Installation 4-36
AC30V Variable Speed Drive
Firmware Update
UPDATING THE DRIVE FIRMWARE
Prepare SD card
Copy the new firmware to an SD card, ensure the file is named firmware.30x
New firmware is available at www.parker.com/ssd/pdq or can be copied from the Parker Drive Quicktool “Drive Maintenance” task.
Perform the upgrade
CAUTION: DO NOT REMOVE POWER FROM THE DRIVE DURING THE FIRMWARE UPDATE.
Insert the SD in the Drive’s SD slot. Replace the GKP if necessary. The ”Update Firmware” will now be
visible in the main menu.
Once you select the “Update Firmware” menu you must edit (1002) Update Firmware to start the
update, change the value from FALSE to TRUE.
The Drive will restart with the setup wizard once the process is complete.