EasyManuals Logo

Parker AC30 series User Manual

Parker AC30 series
453 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #221 background imageLoading...
Page #221 background image
Compliance C-30
AC30V series Variable Speed Drive
Supply Harmonic Analysis (Frame G - Normal Duty)
Assumptions: Rsce 120 at 400V where Q
1n
is the rated rms value of the fundamental voltage of the supply
transformer. The results conform to IEC61000-3-12:2011.
Fundamental Voltage (V)
400
Drive Type
Three Phase
Motor Power
(kW)
22 30 37
22 30 37
Typical Motor
Efficiency %
83 83 83
83 83 83
Harmonic No.
RMS Current (A)
Harmonic No.
RMS Current (A)
1
36.282
49.540
60.995
25
0.930
1.225
1.583
3
0.003
0.001
0.005
27
0.001
0.000
0.000
5
12.848
18.710
20.966
29
0.869
1.162
1.468
7
6.908
10.274
11.144
31
0.712
0.940
1.211
9
0.000
0.000
0.001
33
0.001
0.001
0.001
11
3.072
4.174
5.167
35
0.657
0.882
1.110
13
2.108
2.893
3.533
37
0.557
0.739
0.946
15
0.000
0.000
0.000
39
0.001
0.001
0.001
17
1.769
2.382
2.987
40
0.000
0.000
0.000
19
1.288
1.712
2.188
Total RMS
Current (A)
39.473 54.33 65.95
21
0.000
0.000
0.000
23
1.196
1.604
2.020
* THD (I) %
45.72
47.43
43.22
* (Total Harmonic Distortion)
THD(V) x 100
=
=
Q
Q
h
2
1
n
h
40
=
h
2
%
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals