C-35 Compliance
AC30V series Variable Speed Drive
The wire sizes allow for an ampacity of 125% of the rated input and output amperes for motor branch-circuit conductors as specified in
NEC/NFPA-70.
FRAME D
Terminal acceptance range: 30-10 AWG
Model Number
Power Input AWG
Power Output AWG
Brake Output / DC AWG
400V Build Variant: 380-480V ±10%
NORMAL
DUTY
31V-4D0004-..
14
14
14
31V-4D0005-..
14
14
14
31V-4D0006-..
14
14
14
31V-4D0008-..
14
14
14
31V-4D0010-..
14
14
14
31V-4D0012-..
14
14
14
HEAVY
DUTY
31V-4D0004-..
14
14
14
31V-4D0005-..
14
14
14
31V-4D0006-..
14
14
14
31V-4D0008-..
14
14
14
31V-4D0010-..
14
14
14
31V-4D0012-..
14
14
14
FRAME E Terminal acceptance range: 30-10 AWG
Model Number
Power Input AWG
Power Output AWG
Brake Output / DC AWG
400V Build Variant: 380-480V ±10%
NORMAL
DUTY
31V-4E0016-..
12
12
14
31V-4E0023-..
10
10
14
HEAVY
DUTY
31V-4E0016-..
14
14
14
31V-4E0023-..
12
12
14
FRAME F Terminal acceptance range: 18-6 AWG
Model Number
Power Input AWG
Power Output AWG
Brake Output / DC AWG
4
00V Build Variant: 380-480V ±10%
NORMAL
DUTY
31V-4F0032-.. 8 8 12
31V-4F0038-.. 8 8 10
HEAVY
DUTY
31V-4F0032-.. 10 10 12
31V-4F0038-.. 8 8 10