Parameter Reference D-77
AC30V series Variable Speed Drive
PNO Parameter Descriptions
0477 PMAC SVC Start Time
This parameter is used in conjunction with the PMAC SVC Open Loop Strt parameter. It selects the duration of Step 1 in the startup
procedure used for starting motors:
The value should be set up relatively to the motor inertia + load inertia.
0478 PMAC SVC Start Cur
This parameter is used in conjunction with the PMAC SVC Open Loop Strt parameter. It selects the current level during the startup
procedure used for starting motors.
The percentage value is a percentage of the nominal motor current (PMAC Rated Current of the PMAC Motor Data functions)
.
The default value of 10% is considered appropriate for most applications with light load, very low friction and low acceleration.
The value should be adapted to the starting conditions.
0479 PMAC SVC Start Speed
This parameter is used in conjunction with the PMAC SVC Open Loop Strt parameter. It selects the speed setpoint at which the
speed control is switched from an open loop mode to a closed loop mode during the startup procedure used for starting motors.
The percentage value is a percentage of the maximum application speed (100% Speed in RPM of the Scale Setpoint functions). It
should be set to an equivalent of 5% of the PMAC Max Speed of PMAC Motor Data function.
In open loop mode, the system is not controlled in speed mode. It must only be used to ‘start’ the motor under heavy conditions, or to
transitorily reach the zero speed or crossing the zero speed setpoint. It is not intended to be used to control accurately a motion.
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals