Analog input and output parameter group 02
PARAMETER DESCRIPTION 111
5.3.11 Maximum analog output reference
Set display reference for terminal AM/FM when output frequency or current.
Maximum analog output
frequency reference
50Hz system(when 00-24(P.189)=1)
60Hz system(when 00-24(P.189)=0)
Maximum analog output
current reference
Frame D and the types below
Maximum output reference
Terminal AM/FM maximum analog output value corresponds to 02-51(P.55) value..
Terminal AM/FM maximum analog output value corresponds to 02-52(P.56) value.
Note: Default value for 02-52(P.56) is determined by motor types.
5.3.12 Terminal AM/FM fixed output level
Makes AM/FM output a fixed level signal.
Terminal AM/FM fixed
output level
Set 02-54(P.541) to 0~100.0%, which corresponds to 0~10V/20mA of AM;
For example: 02-54(P.541) =50%, the output of AM is 10V*50%=5V.
5.3.13 PT100 level setting
Sets PT100 protection level and operation frequency
PT100 thermistor
voltage level 1
If PT100 voltage is higher than level 1, output frequency
will decrease to 02-57 (P.594) after 02-58 (P.595) setting
time.
PT100 thermistor
voltage level 2
If PT100 voltage is higher than level 2, act correspondingly
according to the settings of 06-15 (P.533).
PT100 thermistor
level 1 frequency
When PT100 voltage is higher than level 1, output frequency will
decrease to 02-57 (P.594)
PT100 thermistor
level 1 delay time
Action delay time when output frequency decreases to 02-57 (P.594)
PT100 level setting