Protection parameter group06
PARAMETER DESCRIPTION 148
5.7 Protection parameter group 06
Group
Parameter
Number
Name
Setting Range
Default
Page
06-00
P.9
Electronic thermal relay
capacity
0~500.00A
0.00A
151
06-01
P.22
Stall prevention operation
level
0~250.0%
150.0%
151
06-02
P.23
Stall prevention operation
level correction factor
0~150.0%
99999
151
99999: Stall prevention operation level is the
setting value of 06-01(P.22).
06-03
P.66
Stall prevention operation
reduction starting
frequency
50Hz system: 0~650.00Hz
50.00Hz
151
60Hz system: 0~650.00Hz
60.00Hz
06-04
P.220
Acceleration and
deceleration time when
current stall
0: According to the current Acc/Dec time
3
151
1: According to the first Acc/Dec time
2: According to the second Acc/Dec time
3: Automatically calculate proper Acc/Dec time
06-05
P.30
Regenerative brake
selection
0: Brake duty is fixed at 3%, parameter
06-06(P.70) will be off.
0
153
1: Brake duty is 06-06(P.70) value.
2:Connet to brake unit(D frame and above)
2
06-06
P.70
Special regenerative brake
duty
0~100.0%
0.0%
153
06-07
P.263
Decrease carrier protection
setting
0: Fixed carrier frequency, and limit output
current according to carrier value.
0
153
1: Fixed rated current, and limit carrier according
to output current and temperature.
06-08
P.155
Over torque detection level
0~200.0%
0.0%
155
06-09
P.156
Over torque detection time
0.1~60.0s
1.0s
155
06-10
P.260
Action when detect over
torque
0: OL2 alarm will not be reported after over
torque detection, and inverter keeps running.
1
155
1: OL2 alarm will be reported after over torque
detection, and inverter stops.
06-11
P.160
Stall level when restart
0~150.0%
100.0%
156
06-12
P.245
Cooling fan operation
0: Fan turn on when inverter starts running. Fan
turn off 30 seconds after inverter stops.
0
156
1: Fan turn on when inverter power on. Fan turn
off when inverter power off.
2: Fan turn on if heat sink temperature is higher
than 40℃. Fan turn off when inverter power off
3: Fan turn on if heat sink temperature is higher
than 60℃. Fan turn off when heat sink
temperature is lower than 40℃.

Table of Contents

Other manuals for Shihlin electric SE3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SE3 Series and is the answer not in the manual?

Shihlin electric SE3 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSE3 Series
CategoryInverter
LanguageEnglish

Related product manuals