Application parameter group 10
PARAMETER DESCRIPTION 214
5.11.4 Restart mode selection
Select suitable start mode according to different load conditions.
Parameter
Name
Default
Setting Range
Content
10-08
P.150
Restart mode selection
0
xx0
No frequency search.
xx1
Direct frequency search
xx2
Decrease voltage mode
x0x
Power on once.
x1x
Start each time.
x2x
Only instantaneous stop and restart
0xx
No rotation direction detection.
1xx
Rotation direction detection.
2xx
00-15(P.78)=0, rotation direction detection
00-15(P.78)=1,2, no rotation direction detection.
10-09
P.57
Restart idling time
99999
030.0s
---
99999
Off.
10-10
P.58
Restart rising time
5.0s
060.0s
7.5K (included) and types below.
10.0s
11K22K types
Restart mode selection
10-08(P.150) is set by 4 bits. The meaning of each bit is as follows:
10-08
(P.150)
=
0
No frequency search
1
Immediate frequency search
2
Cheapen voltage
0
One electrify
1
Every starting
2
Stop momentary
0
No detection of rotation
1
The detection of rotation
2
00-15(P.78)=0,The direction of rotation
00-15(P.78)=1,2, No direction of rotation
Note: 1. 10-08(P.150) must also be set if need instant restart function.
2. If 10-08(P.150) is not 0, in default inverter do linear acceleration and deceleration.
3. The direction detection bit of 10-08(P.150) is only valid for direct frequency search.
4. This function is only valid in V/F control mode (00-21(P.300)=0).
Restart function
During motor operation, when instantaneous power interruption occur inverter will stop output immediately. If
10-09(P.57)=99999, inverter will not restart automatically after power is restored; If 10-09(P.57)=0.1~30, when power
is restored, inverter will automatically restart the motor after idling for a period of time (10-09(P.57) value).
When restarting the motor automatically, output frequency is target frequency, but output voltage is zero and then
slowly rises to the proper voltage value. This voltage rise time is called “Restart rising time (10-10(P.58))”.
Setting
Setting

Table of Contents

Other manuals for Shihlin electric SE3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SE3 Series and is the answer not in the manual?

Shihlin electric SE3 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSE3 Series
CategoryInverter
LanguageEnglish

Related product manuals