Protection parameter group06
PARAMETER DESCRIPTION 161
Note: 1. Considering capacitor temperature will affects capacity; please wait three hours or longer after power OFF
before testing.
2. Capacitor lifetime detection can only be operated under V/F mode.
3. Frame A /B are not equipped with capacitor lifetime detection function.
5.7.18 Time record function
It is used to record the inverter accumulative operation time.
Total inverter operation
time (minutes)
Total inverter operation
time (days)
Total inverter power on
time (minutes)
Total inverter power on
time (days)
Time record function
06-27(P.292) is operation minutes of the inverter. The value cannot be changed when 00-02=3(P.998=1) is executed
or power is cut off, but can be cleared when set 06-27(P.292) to 0.
06-28(P.293) is operation days of the inverter. The value cannot be changed when 00-02=3(P.998=1) is executed or
power is cut off, but can be cleared when set 06-28(P.293) to 0.
5.7.19 Output power calculation
Output power (lower 16
bits)
There are two decimals, read only and can be written to 0
Output power (higher
16 bits)
Read only and can be written to 0
Output power value=06-32(P.299)*2
16
+06-31, and unit is KWH.
5.7.20 Alarm query function
This function provides users with information about latest 12 alarm codes.
06-40 (P.288) value 1~12 corresponds to 06-41(P.289)’s
alarm E1~E12.
Alarm record code
display