Communication parameter group07
PARAMETER DESCRIPTION 180
Communication command list
Set the following command codes and data to perform various operation control, monitoring, etc.
Shihlin protocol
command code
Data content and function description
H0000: Communication mode;
H0001: External mode;
H0002: JOG Mode;
H0003: Combined mode 1;
H0004: Combined mode 2;
H0005: Combined mode 3;
H0006: Combined mode 4;
H0007: Combined mode 5;
H0008: PU Mode;
00000000
b7 ~ b0
b11 ~ b8
Setting value
of 00-17
Setting value
of 00-18
b14 ~ b12b15
1
Inverter status
monitoring
H0000~H00FF
b15: during tuning
b14: during inverter reset
b13, b12: Reserved
b11: inverter EO status
b10:PLC operating
b9: inverter under voltage
b8: inverter voltage stall
b7: alarm occurred
b6: frequency detect
b5: reserved
b4: overload
b3: frequency arrive
b2: during reverse rotation
b1: during forward rotation
b0: running
Target
frequency
write-in
Special monitor
codes read out
H0000~H0010: monitor selected information.
Please refer to special monitoring code table (H0009
reserved)
Special monitor
codes write in
Monitor external
operation
b0b3
b2 b1
b15~b4
RESSTF
STR
MRS
0000 0000 0000
H9696: function of 00-02=2/P.997=1.
When communicating with upper controller, inverter
cannot return data to upper controller because
inverter is reset.