Tension control parameter group 14
PARAMETER DESCRIPTION 258
5.15.1 Tension control mode selection
Tension control mode selection
Tention control mode
selection
Open-loop torque control mode(Under closed-loop vector
control)
Closed-loop speed control mode
Closed-loop torque control mode(Under closed-loop vector
control mode)
Linear speed control mode
Tightening roll option
when releasing
Forbid tightening material during start-up
Allow tightening material during start-up
Mechanical transfer
ratio
Mechanical transfer ratio
Tension control mode
When 14-00
(P.600)
is 0,tension control invalid,inverter is identical to general inverter.
When 14-00
(P.600)
is 1,opened-loop torque control mode is activated.The inverter keeps the tension consistent
through controlling the output torque of the motor.Tension feedback is not required,but speed detection encoder
must be installed when the inverter is working under closed-loop vector control mode.
When 14-00
(P.600)
is 2,closed-loop speed mode is activated.The controlling result is to make the tension(position)
feedback signal stable at the value given by PID.
Closed-loop means that tension (position) detection feedback is required to form a closed-loop
adjustment.Speed control mode means that the inverter adjusts frequency according to feedback signal to achieve
control.This program is operable in any motor control mode,i.e. 00-21 is able to be set to 0~4.
When 14-00
(P.600)
is 3,closed-loop torque control mode is activated.Tension feedback closed-loop adjustment is
added on the basis of opened-loop tension control.The tension signal fed back by the tension detection device and
the tension setting value constitute the PID closed-loop adjustment which is used to adjust the inverter output
torque reference.The control method of it works under closed-loop vector control.The speed encoder must be
installed.
When 14-00
(P.600)
is 4,constant linear speed mode is activated.This is a special application in order to exclude the
need of PID adjustment in operating constant linear control,which is more stable than the normal closed-loop
control and applicable to some situations that require stable operation and doesn’t require rapidly adjusting linear
speed. This program is operable in any motor control mode,i.e. 00-21 is able to be set to 0~4.