EasyManua.ls Logo

Siemens 6MD86 - Page 101

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The communication ring has the advantage over the communication chain that the entire communications
system and, for example, the differential protection function also work if one of the communication connec-
tions fails or if a device in the topology is taken out of operation.
You can find more information in chapter 3.5.2.5 Device-Combination Settings.
The devices detect failure or logging off, and switch over automatically to the remaining communication
routes.
The following figure shows, for example, a four-line-end differential-protection application if all protection
communications are of type 1. A typical application with protection communications of type 2 is the exchange
of indications and measured values between 4 devices (for example, between switchgears), whereby the
connection can occur via different communication routes. This is the application for a protection-data trans-
mission device.
[dwringto-030211-01.tif, 1, en_US]
Figure 3-43 4 SIPROTEC Devices in a Ring Topology
i
i
NOTE
If a connection fails in the ring topology, this configuration continues to function as a chain topology. In
addition, a device in the constellation can be logged off from the topology.
Protection-Interface Information Transfer
With the protection-interface information transfer, customer-specific indications and measured values can be
communicated via the protection interface with settable update cycles (priorities).
There are 3 different priorities when transferring protection-interface information:
Priority 1: Use Priority 1 for the transmission of fast protection signals that are transferred and updated
at a maximum of every 20 ms in a telegram.
Priority 2: Use Priority 2 for the transmission of fast single-point or double-point indications that are
transferred and updated at a maximum of every 40 ms.
Priority 3: Use Priority 3 for all indications, measured, and metered values that are transferred and
updated a maximum of every 100 ms.
The number of customer-specific signals, indications, and measured values conform with the remaining band-
width. The remaining bandwidth is lower than with all other protection functions (type 2) when using a differ-
ential protection (type 1). Customer-specific measured values consume more bandwidth than single-point
indications.
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual 101
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals