EasyManua.ls Logo

Siemens 6MD86 - Application and Setting Notes; Settings; Information List; Voltage Phase-Rotation Supervision

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application and Setting Notes
Parameter: Threshold
Recommended setting value (_:3) Threshold = 25 V
The Threshold parameter is used to set the voltage which the device uses to recognize the calculated fault
voltage (V
F
) as a failure of the voltage sums. Siemens recommends using the default setting.
Parameter: Delay failure indication
Recommended setting value (_:6) Delay failure indication = 5.00 s
Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
Settings
Addr. Parameter C Setting Options Default Setting
Supv. sum V
_:1 Supv. sum V:Mode
off
on
test
off
_:3 Supv. sum V:Threshold 0.300 V to 170.000 V 43.300 V
_:6 Supv. sum V:Delay
failure indication
0.00 sto 100.00 s 5.00 s
Information List
No.
Information Data Class
(Type)
Type
Supv. sum V
_:82 Supv. sum V:>Block function SPS I
_:54 Supv. sum V:Inactive SPS O
_:52 Supv. sum V:Behavior ENS O
_:53 Supv. sum V:Health ENS O
_:71 Supv. sum V:Failure SPS O
Voltage Phase-Rotation Supervision
Overview of Functions
The Voltage phase-rotation supervision function monitors the phase sequence of the secondary-circuit
voltages by monitoring the sequence of the zero crossings (with same sign) of the voltages. This enables the
device to detect connections that were inverted during commissioning. The criterion for the check is the
setting of the Phase sequence parameter.
Structure of the Function
The Voltage phase-rotation supervision function is located in the Power-system data of each 3-phase
voltage measuring point.
8.3.6.4
8.3.6.5
8.3.6.6
8.3.7
8.3.7.1
8.3.7.2
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual 957
C53000-G5040-C015-9, Edition 11.2017