EasyManua.ls Logo

Siemens 6MD86 - Application Notes and Setting Notes for the External 1-Of-N Check Function Block

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[scbbcon6-270313-01.tif, 1, en_US]
Figure 6-57 Spontaneous Status Change
Depending on the transmission reason, the desired control value or the actual state value of the controllable
and the switching device can be contained in the log.
The following table shows the relationship.
Table 6-23
Relationship between the Reason for Transmission and the Value Logged
Reason for Transmission Value
Selected (SEL) Desired value
Operate (OPR) Desired value
Command cancellation (CNC) Desired value
Command execution and termination (CMT) Actual value
Spontaneous change (SPN) Actual value
Application Notes and Setting Notes for the External 1-of-n Check Function
Block
Parameter: Feedba. mon. time release
Default setting (_:101) Feedba. mon. time release = 5.00 s
With the parameter Feedba. mon. time release, you specify the time within which the release request
must be confirmed via the input
>Release active
.
Parameter: Feedba. mon. time reset
Default setting (_:102) Feedba. mon. time reset = 5.00 s
With the parameter Feedba. mon. time reset, you specify the time within which the withdrawal of the
release requests must be confirmed via the input
>Release active
.
6.3.3
Control Functions
6.3 Control Functionality
358 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals