EasyManua.ls Logo

Siemens 6MD86 - Application and Setting Notes

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application and Setting Notes
Routings for Activation of the Circuit Breaker
The following image shows the routings needed:
The device can execute 3-pole tripping (via the protection device).
The device can execute 3-pole opening (via the control).
Furthermore, the device can switch on 3-pole (via the control / AREC)
[loansteu-230311-01.tif, 2, en_US]
Figure 5-25 Activation of the Circuit Breaker
By routing the Trip/open cmd. signals to 1 or 2 binary outputs, you can carry out 1, 1.5, and 2-pole activa-
tions of the circuit breaker. You can find a detailed description of this in chapter 6.2.2.3 Connection Variants
of the Circuit Breaker.
i
i
NOTE
Do not confuse these 1-pole, 1.5-pole, and 2-pole activations of the circuit breaker with 1-pole or 3-pole
tripping of the circuit breaker.
Routing for Analysis of the Circuit-Breaker Switch Position
For certain functions of the device, it is useful to detect the circuit-breaker switch position via its auxiliary
contacts. These data are for example:
Circuit-breaker position recognition function block
Circuit-breaker failure protection function
Control function block
The operating principle of the auxiliary contacts is described in the individual functions.
Siemens recommends capturing the
Circuit breaker is open in 3 poles
and
Circuit breaker
is closed in 3 poles
information via auxiliary contacts. This is the optimal configuration for the
control functionality. For purely protection applications, it is also enough to capture just one of the 2 circuit-
breaker positions.
5.5.7.6
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
220 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals