With the Activate device test mode parameter, you activate the test mode that adds a test bit to the
output indications. If test mode is activated but the test mode of the relay outputs is not, no relay outputs are
activated by the protection functions.
Parameter: Oper.bin.outp. under test
•
Default setting (_:151) Oper.bin.outp. under test = inactive
If you activate the parameter Oper.bin.outp. under test, you can permit the closing of a binary output
for test purposes. In this way, indications are output during a device-wide test mode and the relays are either
activated or not. If an individual function is in test mode, only indications are output and the relays are not
activated.
NOTE
The device remains in test mode during every startup until you intentionally set the device back into
process mode. You set process mode by switching the parameterActivate device test mode to inactive
again (removing the check mark).
Settings
Addr. Parameter C Setting Options Default Setting
Device
_:101 General:Rated frequency
•
50 Hz
•
60 Hz
50 Hz
_:102 General:Minimum
operate time
0.00 s to 60.00 s 0.00 s
_:138 General:Block moni-
toring dir.
•
off
•
on
off
Setting change
_:163 General:Reserv.time for
com.prot.
0 s to 65535 s 120 s
Spontan.indic.
_:139 General:Fault-display
•
with pickup
•
with trip
with pickup
Test support
_:150 General:Activate device
test mode
•
0
•
1
false
_:151 General:Oper.bin.outp.
under test
•
0
•
1
false
Information List
No.
Information Data Class
(Type)
Type
General
_:510 General:>Test mode on SPS I
_:511 General:>Test mode off SPS I
_:507 General:>Device funct.logoff on SPS I
_:508 General:>Dev. funct.logoff off SPS I
_:512 General:>LED reset SPS I
_:52 General:Behavior ENS O
_:53 General:Health ENS O
_:51 General:Test mode ENC C
_:321 General:Protection on SPC C
3.10.2.3
3.10.2.4
System Functions
3.10 Device Settings
SIPROTEC 5, High-Voltage Bay Controller, Manual 167
C53000-G5040-C015-9, Edition 11.2017