Figure 3-82 Signal Change during Chatter Blocking with Permissible Number of Signal State Changes
During 2nd Subsequent Test Time
Acquisition Blocking and Manual Updating
During commissioning, maintenance, or testing, a brief interruption of the connection between the logical
signals and binary inputs may be useful. It allows you to manually update the status of a switching device that
is not providing feedback correctly. Before this can take place, you must first set acquisition blocking.
To set the acquisition blocking, proceed as follows:
In the main menu of the device display, use the navigation keys to move to
CommandsEquipmentAq.blkman. update.
If several switching devices are available, select the appropriate device (for example, a circuit breaker)
using the navigation keys.
Press the Change softkey.
Enter the confirmation ID.
Confirm the process with the softkey marked OK in the display.
After entering the confirmation ID, the acquisition blocking function is switched on.
[scerfass-310816-01, 1, en_US]
Figure 3-83 Activating the Acquisition Blocking
3.8.2
System Functions
3.8 Other Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual 147