Addr. Parameter C Setting Options Default Setting
Stage 2
_:14552:1 Stage 2:Mode
•
off
•
on
•
test
off
_:14552:2 Stage 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:14552:9 Stage 2:External trip
initiation
•
no
•
current
•
light
no
_:14552:8 Stage 2:Operating mode
•
light only
•
current and light
current and light
_:14552:11 Stage 2:Sensor
•
point sensor
•
line sensor
•
custom
point sensor
_:14552:7 Stage 2:Threshold light -34.00 dB to -10.00 dB -20.00 dB
_:14552:10 Stage 2:Channel Setting options depend on
configuration
Stage 3
_:14553:1 Stage 3:Mode
•
off
•
on
•
test
off
_:14553:2 Stage 3:Operate &
flt.rec. blocked
•
no
•
yes
no
_:14553:9 Stage 3:External trip
initiation
•
no
•
current
•
light
no
_:14553:8 Stage 3:Operating mode
•
light only
•
current and light
current and light
_:14553:11 Stage 3:Sensor
•
point sensor
•
line sensor
•
custom
point sensor
_:14553:7 Stage 3:Threshold light -34.00 dB to -10.00 dB -20.00 dB
_:14553:10 Stage 3:Channel Setting options depend on
configuration
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:82 General:>Block function SPS I
_:2311:53 General:Health ENS O
_:2311:301 General:Current detected SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:14551:81 Stage 1:>Block stage SPS I
_:14551:501 Stage 1:>External current SPS I
_:14551:502 Stage 1:>External light SPS I
7.29.7
Protection and Automation Functions
7.29 Arc Protection
918 SIPROTEC 5, High-Voltage Bay Controller, Manual