Addr. Parameter C Setting Options Default Setting
Supervis. grp. end
_:108 Superv.Grp.#:I/O module
ID
•
I/O module 1
•
I/O module 2
•
I/O module 3
•
I/O module 4
•
I/O module 5
•
I/O module 6
•
I/O module 7
•
I/O module 8
•
I/O module 9
•
I/O module 10
•
I/O module 11
•
I/O module 12
•
I/O module 13
•
I/O module 14
•
I/O module 15
I/O module 1
_:109 Superv.Grp.#:Binary
input
1 to 256 1
Information List
No. Information Data Class
(Type)
Type
Superv.Grp.#
_:52 Superv.Grp.#:Behavior ENS O
_:55 Superv.Grp.#:Sig. volt. disturbed SPS O
Voltage-Transformer Circuit Breaker
Overview of Functions
The Voltage-transformer circuit breaker function detects the tripping of the voltage-transformer circuit
breaker due to short circuits in the voltage-transformer secondary circuits.
The Voltage-transformer circuit breaker function works independently of Measuring-voltage failure detec-
tion and should be used – if possible – in parallel to it.
The tripping of the voltage-transformer circuit breaker has an impact on the quality of the recorded measured-
value data (see chapter 3.3 Processing Quality Attributes).
For the following functions the reaction (block/not block) can be set within the function in cases of a tripping
of the voltage-transformer circuit breaker:
•
Overcurrent protection, phases
•
Overcurrent protection, ground
•
Overvoltage protection with 3-phase voltage
•
Overvoltage protection with positive-sequence voltage
•
Overvoltage protection with any voltage
•
Undervoltage protection with 3-phase voltage
•
Undervoltage protection with any voltage
Structure of the Function
The Figure 8-10 shows the position of the function in the device. Every voltage measuring point contains the
Voltage-transformer circuit breaker function.
8.3.3.6
8.3.4
8.3.4.1
8.3.4.2
Supervision Functions
8.3 Supervision of the Secondary System
950 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017