IN Measured
The function operates with the measured ground current IN. This is the
recommended setting unless there is a specific reason to use the calculated
zero-sequence current 3I0.
3I0 Calculated
The function operates with the calculated zero sequence current 3I0. This
setting option can be used when applying a redundant 50N/51N function for
safety reasons.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:9 General:Measured
value
•
3I0 calculated
•
IN measured
IN measured
7.5.3.3
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 637
C53000-G5040-C015-9, Edition 11.2017