AB
Phase C changed over with phase B
NOTE
If you change the setting value of the parameter Inverted phases, consider the following:
The device can take the new setting value only if the binary input signal
>Invert Phases
is not active.
Input signal:
>Phs-rotation reversal
The
>Phs-rotation reversal
binary input is used to switch between the ABC phase sequence and the
ACB phase sequence. The switchover direction depends on the setting of the Phase sequence parameter. In
doing so, the phase sequence of all 3-phase measuring points is changed. Changing of the phase-rotation
reversal via the binary input is only possible if no measurands (< 5 % of the rated variables) are present at all 3-
phase measuring points.
Input signal:
>Invert Phases
The binary input
>Invert Phases
is used to activate the setting of the parameter Inverted phases. In
doing so, the phase sequence of the selected measuring point is changed. Changing of the phase sequence
via the binary input is only possible if no measurand (< 5 % of the rated variables) is present at the respective
3-phase measuring point.
Settings
Addr.
Parameter C Setting Options Default Setting
General
_:101 General:Phase sequence
•
ABC
•
ACB
ABC
General
_:101 VT 3-phase:Rated primary
voltage
0.20 kV to 1200.00 kV 400.00 kV
_:102 VT 3-phase:Rated secon-
dary voltage
80 V to 230 V 100 V
_:103 VT 3-phase:Matching ratio
Vph / VN
0.10 to 9.99 1.73
_:104 VT 3-phase:VT connection
•
3 ph-to-gnd volt. + VN
•
3 ph-to-gnd voltages
•
3 ph-to-ph volt. + VN
•
3 ph-to-ph voltages
3 ph-to-gnd
volt. + VN
_:106 VT 3-phase:Inverted phases
•
none
•
AC
•
BC
•
AB
none
_:111 VT 3-phase:Tracking
•
inactive
•
active
active
_:107 VT 3-phase:Measuring-
point ID
0 to 100 0
7.23.5
Protection and Automation Functions
7.23 Phase-Sequence Switchover
866 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017