Settings
Addr. Parameter C Setting Options Default Setting
Control
_:101 Control:Control model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:102 Control:SBO time-out 0.01 s to 1800.00 s 30.00 s
_:103 Control:Feedback moni-
toring time
0.01 s to 1800.00 s 1.00 s
_:104 Control:Check switching
authority
•
no
•
yes
yes
_:105 Control:Check if pos. is
reached
•
no
•
yes
yes
_:106 Control:Check double
activat. blk.
•
no
•
yes
yes
_:107 Control:Check blk. by
protection
•
no
•
yes
yes
Information List
No.
Information Data Class
(Type)
Type
Control
_:53 Control:Health ENS O
_:58 Control:Cmd. with feedback DPC C
6.3.4
6.3.5
Control Functions
6.3 Control Functionality
SIPROTEC 5, High-Voltage Bay Controller, Manual 359
C53000-G5040-C015-9, Edition 11.2017