Figure 6-25 2-Pole Triggering, Routing in DIGSI
The feedback is routed via the position with the disconnector.
Settings
Addr.
Parameter C Setting Options Default Setting
Disconnector
_:5401:101 Disconnector:Maximum
output time
0.01 s to 1800.00 s 10.00 s
_:5401:102 Disconnector:Seal-in time 0.00 s to 60.00 s 0.00 s
_:5401:103 Disconnector:Switching-
device type
switch-disconnector
disconnector
grounding switch
fast grounding switch
disconnector
Information List
No.
Information Data Class
(Type)
Type
Disconnector
_:5401:500 Disconnector:>Acquisition blocking SPS I
_:5401:501 Disconnector:>Reset switch statist. SPS I
_:5401:53 Disconnector:Health ENS O
_:5401:58 Disconnector:Position DPC C
_:5401:300 Disconnector:Open command SPS O
_:5401:301 Disconnector:Close command SPS O
_:5401:302 Disconnector:Command active SPS O
_:5401:305 Disconnector:Op.ct. INS O
6.2.3.4
6.2.3.5
Control Functions
6.2 Switching Devices
334 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017