Figure 5-22 Definitive Tripping, Circuit-Breaker Tripping Alarm Suppression
Tripping and Opening Information
When a trip or opening command is issued, the breaking information shown in the next figure is saved in the
fault log.
[loausloe-081210-01.tif, 2, en_US]
Figure 5-23 Breaking Information
The following statistics information is saved for the circuit breaker:
Number of switching cycles:
All tripping, opening, and closing operations are counted.
Number of closing operations by the automatic reclosing function
Total of breaking currents
The statistics information can be individually set and reset via the device control. It is also possible to reset all
values via the binary input signal >Reset switch statist..
[lo_statistics information circuit-breaker, 2, en_US]
Figure 5-24 Statistics Information About the Circuit Breaker
5.5.7.5
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual 219
C53000-G5040-C015-9, Edition 11.2017