Addr. Parameter C Setting Options Default Setting
_:106 Time sync.:Time source
2 port
port J
port F
port E
port P
port N
port G
_:107 Time sync.:Time source
2 channel
Ch1
Ch2
_:108 Time sync.:Time zone
time source 1
UTC
local
local
_:109 Time sync.:Time zone
time source 2
UTC
local
local
_:101 Time sync.:Fault indica-
tion after
0 s to 3600 s 600 s
Information List
No. Information Data Class
(Type)
Type
Time managem.
_:300 Time managem.:Daylight saving time SPS O
_:301 Time managem.:Clock set manually SPS O
No. Information Data Class
(Type)
Type
Time sync.
_:303 Time sync.:Status time source 1 SPS O
_:304 Time sync.:Status time source 2 SPS O
_:305 Time sync.:Time sync. error SPS O
_:306 Time sync.:Leap second SPS O
_:307 Time sync.:High accuracy SPS O