Settings
Addr. Parameter C Setting Options Default Setting
General
_:6601:1 General:Mode
•
off
•
on
•
test
on
_:6601:101 General:79 operating mode
•
with op., w/o act. time
•
with op., with act. time
•
w.pickup, w/o act. time
•
w.pickup, w. action time
with op., with
act. time
_:6601:102 General:CB ready check bef.
start
•
no
•
yes
no
_:6601:103 General:Reclai. time
aft.succ.cyc.
0.50 s to 300.00 s 3.00 s
_:6601:104 General:Block. time aft.
man.close
0.00 s to 300.00 s 1.00 s
_:6601:105 General:Start signal
supervis.time
0.01 s to 300.00 s 0.13 s
_:6601:106 General:CB ready superv.
time
0.01 s to 300.00 s 3.00 s
_:6601:107 General:3-pole operate by
79
•
no
•
yes
yes
_:6601:111 General:Max. dead-time
extension
0.00 s to 300.00 s; ∞ 1.20 s
_:6601:114 General:Voltage supervi-
sion time
0.10 s to 30.00 s 0.10 s
_:6601:115 General:Volt. thres.f. live
line/bus
0.300 V to 340.000 V 48.000 V
ADT
_:6631:101 ADT:1-pole trip allowed
•
no
•
yes
no
_:6631:104 ADT:Action time 0.00 s to 300.00 s; ∞ 0.20 s
_:6631:105 ADT:Maximum dead time 0.50 s to 3000.00 s 5.00 s
_:6631:102 ADT:CB ready check
bef.close
•
no
•
yes
no
_:6631:103 ADT:Synchroch. aft. 3-pole
d.t.
•
none
•
internal
•
external
none
_:6631:106 ADT:Intern. synchrocheck
with
Setting options depend on
configuration
Information List
No.
Information Data Class
(Type)
Type
General
_:6601:51 General:Mode (controllable) ENC C
_:6601:87 General:>Function off SPS I
_:6601:524 General:>Function on SPS I
_:6601:347 General:Function on SPC C
_:6601:82 General:>Block function SPS I
_:6601:501 General:>Release by ext.sync. SPS I
7.2.5.2
7.2.5.3
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 581
C53000-G5040-C015-9, Edition 11.2017