i
NOTE
An invalid measuring-point selection (ID < 0 or an ID of a unconnected measuring point) for input
>MP-ID
selection
results in the following:
The voltage measured values are displayed as failure.
The validity of the voltage measured values is set to invalid.
The indication
Health
is set to Alarm.
The indication
Selection invalid
becomes true.
Information List
No. Information Data Class
(Type)
Type
V-MP selection
_:501 V-MP selection:>MP-ID selection INS I
_:53 V-MP selection:Health ENS O
_:301 V-MP selection:Selection invalid SPS O
5.9.4
Function-Group Types
5.9 Voltage Measuring-Point Selection
302 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017