has been exceeded. Either the frequency is out of range (10 Hz to 80 Hz) or the input signals are too small for
a manual update. Should this condition occur, the system switches the update frequency to a sampling rate
that corresponds to the rated frequency.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Phase sequence
ABC
ACB
ABC
General
_:8911:101 VT 3-phase:Rated primary
voltage
0.20 kV to 1200.00 kV 400.00 kV
_:8911:102 VT 3-phase:Rated secon-
dary voltage
80 V to 230 V 100 V
_:8911:103 VT 3-phase:Matching ratio
Vph / VN
0.10 to 9.99 1.73
_:8911:104 VT 3-phase:VT connection
not assigned
3 ph-to-gnd volt. + VN
3 ph-to-gnd voltages
3 ph-to-ph volt. + VN
3 ph-to-ph voltages
2 ph-to-ph volt. + VN
2 ph-to-ph voltages
2 ph-to-gnd volt. + VN
2 ph-to-gnd voltages
3 ph-to-gnd
volt. + VN
_:8911:106 VT 3-phase:Inverted phases
none
AC
BC
AB
none
_:8911:111 VT 3-phase:Tracking
inactive
active
active
_:8911:130 VT 3-phase:Measuring-
point ID
0 to 100 0
Voltage transformers1 - 4
_:3811:103 VT 1:Magnitude correction 0.010 to 10.000 1.000
_:3811:108 VT 1:Phase
V A
V B
V C
V AB
V BC
V CA
VN
Vx
General
_:8881:115 CT 3-phase:CT connection
not assigned
3-phase + IN
3-phase
3-phase + IN-separate
3-phase, 2 primary CT
3ph,2prim.CT + IN-sep
2ph, 2p. CT + IN-sep
2 phase + IN
3-phase + IN-
separate
5.1.6
Function-Group Types
5.1 Power-System Data
SIPROTEC 5, High-Voltage Bay Controller, Manual 189
C53000-G5040-C015-9, Edition 11.2017