Communication with 20-mA Unit Ethernet
Logic
[lo20mtcp-150113-01.tif, 1, en_US]
Figure 5-55
Logic of the Function 20-mA Unit Ethernet
Communication with 20-mA Unit
The function is used to communicate with a 20-mA unit connected via an Ethernet connection. When a
connection of the function to an external 20-mA unit via an Ethernet interface has successfully been estab-
lished, the 20-mA unit sends the measured values of all connected channels to the function 20-mA unit.
Ether.. For the connection to be established successfully, specific communication settings must be specified.
You can find more detailed information in Chapter 5.7.3.4 Application and Setting Notes .
The 20-mA measurement unit 7XV5674 is supported.
Error Responses
The following table lists the conditions under which the
Health
status transitions to the Alarm or Warning
state.
Table 5-8
Error Responses
Error Description Status Health
The function 20-mA unit Ether. cannot establish a
connection with a communication module.
Alarm
The function 20-mA unit Ether. sends TCP settings to
the communication module, which evidently would
like to connect to the 20-mA unit via a serial protocol.
This communication module does not establish a
connection to the 20-mA unit.
Alarm
The connection between the communication module
and the 20-mA unit causes a time-out indication.
Warning
5.7.3.3
Function-Group Types
5.7 Function-Group Type Analog Units
256 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017