EasyManua.ls Logo

Siemens 6MD86 - Process Monitor; Overview of Functions; Structure of the Function

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Process Monitor
Overview of Functions
All function groups that have functions with dependencies on the state of the protected object contain a
process monitor. The process monitor detects the current state of the protected object.
Structure of the Function
The Process monitor function is used in the Standard V/I 3-phase protection function group.
The Process monitor function is provided by the manufacturer with the following function blocks:
Cold-load pickup detection (optional)
Current-flow criterion
Circuit-breaker condition
Closure detection
[dwpro3pt-061212-01.tif, 2, en_US]
Figure 5-92 Structure/Embedding of the Function
You can activate the cold-load pickup detection as needed. All other stages of the process monitor run perma-
nently in the background and are not displayed in DIGSI.
The following figure shows the relationships of the individual function blocks.
5.8
5.8.1
5.8.2
Function-Group Types
5.8 Process Monitor
292 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86