Parameter Value Description
on
Because of the application, it makes sense that the stage is only active (that
is, not blocked) when a certain current flow is present (see note).
off
Current flow monitoring does not make sense for the application.
i
i
NOTE
Because of the flexible setting options of the voltage measurand, the function itself does not determine the
current associated with the voltage. A suitable current-flow monitoring function must be created by the
user with the Continuous Function Chart (CFC), and connected to the binary input signal >Current
flow-criterion.
Operation as Supervision Function
If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Current-flow
criterion
off
on
on
Stage 1
_:571:1 Stage 1:Mode
off
on
test
off
_:571:2 Stage 1:Operate &
flt.rec. blocked
no
yes
no
_:571:9 Stage 1:Measured value
VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:571:8 Stage 1:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
_:571:3 Stage 1:Threshold 0.300 V to 340.000 V 80.000 V
_:571:4 Stage 1:Dropout ratio 1.01 to 1.20 1.05
_:571:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:572:1 Stage 2:Mode
off
on
test
off
_:572:2 Stage 2:Operate &
flt.rec. blocked
no
yes
no
7.17.5
Protection and Automation Functions
7.17 Undervoltage Protection with Any Voltage
822 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017