Negative-Sequence Protection
Overview of Functions
The function Negative-sequence protection (ANSI 46):
Detects 1-phase or 2-phase short circuits in the electrical power system with clearly increased sensitivity
compared to the classical overcurrent protection
Protects electric machines during excessive unbalanced load
Reports unbalanced load conditions in the electricity supply system
Detects phase interruptions in the primary system
Locates short circuits or inversions in the connections to the current transformers
Structure of the Function
The Negative-sequence protection function is used in protection function groups with current measure-
ment.
The function is preconfigured by the manufacturer with 2 Definite-time negative-sequence protection
stages.
In the function Negative-sequence protection, the following stages can be operated simultaneously:
3 stages Definite-time negative-sequence protection
2 stages Inverse-time negative-sequence protection
The stages have an identical structure. Stages that are not preconfigured are shown in gray in the following
figure.
[dwnspstr-271112-01.tif, 3, en_US]
Figure 7-183 Structure/Embedding of the Function
If the device is equipped with the Inrush-current detection function, the stages can be stabilized against
operate due to transformer-inrush currents.