With this parameter, you specify the time delay of the fast step down mode. If the actual voltage is greater
than the value of the limit for the fast step down mode (_:122), the fast step down mode is activated. A fast
step down mode is not activated if the voltage limit is exceeded for only a brief period within the time delay.
Parameter: Function monitoring
Default setting (_:124) Function monitoring = 15 min
You can delay the pickup of the function monitor. With the setting Function monitoring = 0 min, the
function monitor is switched off.
Grid Coupling Transformer Only:
Parameter: Power-flow supervision
Default setting (_:16351:162) Power-flow supervision = on
With the Power-flow supervision parameter, you monitor the power flow. You can switch the param-
eter on or off.
Parameter:
Regulate with T2 at start
Default setting (_:14011:155) Regulate with T2 at start = on
With the Regulate with T2 at start parameter, you can activate a shorter time than T1. This can be
necessary for controlling a voltage recovery or after switching on a transformer. If voltage was not present
beforehand, this setting controls with the shorter time T2 when starting the control action. You can switch
this functionality on or off. If you always want to use the time T2 for control, you must set the
Block T1
controllable to On.
For the three-winding transformer, the address of the Regulate with T2 at start parameter is
_:15601:163 while it is _:16351:163 for the grid coupling transformer.
Parameter: Set point mode active
Default setting (_:14011:160) Set point mode active = on
With the Set point mode active = on parameter, you can send a target voltage to the controller via a
communication network. The voltage controller uses the specified voltage value as target voltage. If the
controller does not receive any valid voltage values, it uses the original target voltage. You can enable or
disable the parameter.
For the three-winding transformer, the address of the parameter Set point mode active is
_:15601:171, for the grid coupling transformer, it is _:16351:171.
Line Compensation
Parameter: Line drop compensation
Default setting (_:14011:125) Line drop compensation = off
You can use the Line drop compensation parameter to select the correction procedure of the load-
dependent line voltage drop. There are 2 procedures available for selection: LDC-Z and LDC-XandR.
For setting the parameter Line drop compensation = LDC-Z, consider the following parameter:
Parameter: Target voltage rising
Default setting (_:14011:126) Target voltage rising = 4.0 %
With the Target voltage rising parameter, you set the voltage drop across the line. The value repre-
sents the voltage rising in % of the Target voltage 1 that occurs at rated load. Only the magnitude of the
current is considered. The set value is added to Target voltage 1.
Set point value increase [%] = ΔV
load
[%] if I
load
= 100 %
[foschlst-211013, 2, en_US]
where:
6.9.4.4
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 495