Then select the Select constellation text box to select the number of devices (see next figure).
Depending on the device, the selection of constellations can be restricted to 2 or 3 devices.
[scconfws-241110-01.tif, 1, en_US]
Figure 3-55 Selecting the Constellation
NOTE
You have the option of changing the number of devices (for example 2 protection communication
devices) depending on the product code any way you like via the Select constellation text box.
If you change the number of devices via the Select constellation text box, all activated constellation
settings are lost.
If the module slot is not yet provided with modules, proceed as follows:
•
Select the desired communication module in the rear view of the device.
•
Select the module from the catalog and drag it to a channel. Thus is the channel configured with a
module. DIGSI 5 indicates whether the module can be used for protection communication under Device
Information.
•
Use the Communication protocols text box to select the protection interface. A text box entitled Protec-
tion interface will then appear (see Figure 3-54).
•
Then use the Select constellation text box to select the number of devices (for example 2 devices
protection com.) (see Figure 3-55).
Device-Combination Settings
Make the device-combination settings and the settings for protection communication (see next figure).
3.5.2.5
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual 109
C53000-G5040-C015-9, Edition 11.2017