Write-Protected Settings
Parameter: Rated apparent power
•
Default setting (_:103) Rated apparent power = 692.82 MVA
With the Rated apparent power parameter, you can set the primary rated apparent power for the auto
transformer to be protected. The Rated apparent power parameter is relevant for the main protection
function of the device. The Rated apparent power set here is the reference value for the percentage-
measured values and setting values made in percentages.
NOTE
If the device works with the IEC 61850 protocol, then you change the setting value of the parameter only
via DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.
The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr. Parameters C Range of Values Default Setting
Network data
_:103 General:rated apparent
power
0.20 MVA to 5 000.00 MVA 692.82 MVA
NOTE
You can find more detailed information on the Process monitor in chapter 5.8 Process Monitor.
Settings
Addr.
Parameter C Setting Options Default Setting
Rated values
_:9451:101 General:Rated current 1 A to 100000 A 1000 A
_:9451:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Power-system data
_:9451:149 General:Power-sys.
neutral point
•
grounded
•
suppress. coil grounded
•
isolated
grounded
Measurements
_:9451:158 General:P, Q sign
•
not reversed
•
reversed
not reversed
Information List
No.
Information Data Class
(Type)
Type
General
_:9451:52 General:Behavior ENS O
_:9451:53 General:Health ENS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O