Figure 3-103 External Push-Button Wiring for Logging off the Device
If a switch is being used for control, route the binary input
>Device funct.logoff on
as H (active
with voltage) and the binary input
>Dev. funct.logoff off
as L (active without voltage).
If the switch S is closed, the device is logged off.
[loextsx logoff device, 1, en_US]
Figure 3-104 External Switch Wiring for Logging off the Device
Indications
The logged-off device reports the status (
(_:315) Device logged off
) and the cause of the logoff.
If you have logged off the device via binary inputs, the indication
(_:313) Logged off via BI
is issued.
If you have logged off the device via on-site operation, via DIGSI 5, or via the protection interface, the indica-
tion
(_:314) Logged off via control
is issued.
The indications are stored in the operational log.
Information List
No.
Information Data Class
(Type)
Type
General
_:507 General:>Device funct.logoff on SPS I
_:508 General:>Dev. funct.logoff off SPS I
_:319 General:Device logoff SPC C
_:313 General:Logged off via BI SPS O
_:314 General:Logged off via control SPS O
_:315 General:Device logged off SPS O