Table 10-1 Example Settings for the System Data
Parameters Value
Power system → VT 3-phase:Rated primary voltage V
CT-prim
15 kV
Power system → VT 3-phase:Rated secondary voltage V
CT-sec
110 kV
Voltage cont. 2w → General:Rated voltage V
rated
10.5 kV
Target voltage 1 V
target
11 kV
This results in the secondary voltage V
act-sec
with a phase-to-ground connection being:
[fo_ibs_prim_measur_volt_4, 1, en_US]
Further Tests
Control Deviation
•
Check the control deviation D = 0 % at set point value infeed.
•
Check the measured value of the control deviation D online in DIGSI or on the on-site operation panel of
the device.
Secondary infeed values for the example:
Voltage-transformer connection phase-to-ground: V
act-sec
= 46.6 V
Voltage-transformer connection phase-to-phase: V
act-sec
= 46.6 V ⋅√3 = 80.7 V
Command Outputs
•
Check the output of the Lower adjusting command after the parameterizable time T1.
With a set bandwidth B of 1 %, this results in the secondary pickup value:
Voltage-transformer connection phase-to-ground: V
act-sec
> 47.1 V
Voltage-transformer connection phase-to-phase: V
act-sec
> 47.1 V ⋅√3 = 81.5 V
•
Check the output of the Higher adjusting command after the parameterizable time T1.
With a set bandwidth B of 1 %, this results in the secondary pickup value:
Voltage-transformer connection phase-to-ground: V
act-sec
< 46.1 V
Voltage-transformer connection phase-to-phase: V
act-sec
< 46.1 V ⋅√3 = 79.8 V
•
Check the output of the Lower adjusting command after the parameterized time Fast step down T
delay.
For the set parameter Fast step down limit = 6 %, the following secondary pickup values result:
Voltage-transformer connection phase-to-ground: V
act-sec
> 49.3 V
Voltage-transformer connection phase-to-phase: V
act-sec
> 49.3 V ⋅√3 = 85.3 V
•
Check the output of the Higher adjusting command after the parameterized time Fast step up T
delay.
For the set parameter Fast step up limit = -6 %, the following secondary pickup values result:
Voltage-transformer connection phase-to-ground: V
act-sec
< 49.3 V
Voltage-transformer connection phase-to-phase: V
act-sec
< 49.3 V ⋅√3 = 85.3 V
Blockings
•
Check the undervoltage blocking V< Blocking.
For the set parameter V< Blocking = 8 kV, the following secondary pickup values result:
10.10.1.4
Functional Tests
10.10 Commissioning Hints for Voltage Control