EasyManua.ls Logo

Siemens 6MD86 - Application and Setting Notes

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[dw_kick-pulse_freq-adj-com, 1, en_US]
Figure 6-82 Kick Pulse and Frequency Adjustment Ranges
Stabilization and Supervision Actions
The parameter Smoothing causes a smoothing of the relevant measuring signal (dV and df) via a recursive
filter. The smoothing of the signals prevents wrong balancing commands from being issued to control the
voltage and frequency in case of a strong fluctuation of the signals. The smoothing has a low-pass behavior
corresponding to a delay element of the 1st order (for PT1 behavior, see also Figure 6-89).
When the voltage and the frequency are adjusted simultaneously, you must ensure that the admissible over-
excitation limit for the generator is not exceeded. The overexcitation is determined by monitoring the (V/
V
rated
)/(f/f
rated
) ratio and compared to the admissible threshold value (parameter (V/Vrated)/(f/frated)).
When the threshold value is exceeded, a voltage balancing command is issued. In this way, the generator
returns to the admissible operating range. The maximum admissible voltage threshold (V2
max
) for V2 is deter-
mined using the overexcitation parameter and the f2/f
rated
ratio.
A generator can only be synchronized with a system when there is a certain amount of slip. The frequency
difference is a measure for the slip within the functionality. A practically constant frequency difference is
assumed when determining the switching point. When adjusting the frequency, take care that no frequency
balancing commands are issued near a potential switching point. When the frequency is in the admissible
band (parameters Max. frequency diff. f2>f1 and Max. frequency diff. f2<f1; see also
Figure 6-82), the currently determined angle difference of the voltage (dα) is used to calculate the speed of
change (dα/dt). This can be used to calculate the remaining time up to the synchronized point (dα → 0)
continuously. If the determined time reaches of the value for the parameter T close without balancing
or falls below it, a frequency balancing command will no longer be issued and any active frequency adjust-
ment will be discontinued.
Application and Setting Notes
Use the Synchronous/asynchronous stage type with balancing commands (Syn./Asy.bal.) for synchro-
nizing generators automatically.
You can find the Syn./Asy.bal. stage in the DIGSI 5 library under FG Circuit BreakerSynchronization
Function extensions.
6.4.9.2
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 395
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals