Addr. Parameter C Setting Options Default Setting
_:691:106 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: bin.input
_:691:34 Inverse-T 1:Effected by
binary input
no
yes
no
_:691:41 Inverse-T 1:Stage
blocked
no
yes
no
_:691:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:107 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Information List
No. Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:691:81 Inverse-T 1:>Block stage SPS I
_:691:84 Inverse-T 1:>Activ. dyn. settings SPS I
_:691:500 Inverse-T 1:>Block delay & op. SPS I
_:691:54 Inverse-T 1:Inactive SPS O
_:691:52 Inverse-T 1:Behavior ENS O
_:691:53 Inverse-T 1:Health ENS O
_:691:60 Inverse-T 1:Inrush blocks operate ACT O
_:691:62 Inverse-T 1:Dyn.set. AR cycle1act. SPS O
_:691:63 Inverse-T 1:Dyn.set. AR cycle2act. SPS O
_:691:64 Inverse-T 1:Dyn.set. AR cycle3act. SPS O
_:691:65 Inverse-T 1:Dyn.set. ARcycl.>3act SPS O
_:691:66 Inverse-T 1:Dyn.set. CLP active SPS O
_:691:67 Inverse-T 1:Dyn.set. BI active SPS O
_:691:68 Inverse-T 1:Dyn. set. blks. pickup SPS O
_:691:59 Inverse-T 1:Disk emulation running SPS O
_:691:55 Inverse-T 1:Pickup ACD O
_:691:56 Inverse-T 1:Operate delay expired ACT O
_:691:57 Inverse-T 1:Operate ACT O
_:691:302 Inverse-T 1:I0el.Iph WYE O
Stage with User-Defined Characteristic Curve
Description
This stage is only available in the advanced function type.
This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage (see
chapter 7.4.5.1 Description ). The only differences are as follows:
7.4.5.4
7.4.6
7.4.6.1
Protection and Automation Functions
7.4 Overcurrent Protection, Phases
622 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017