Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 7.5.7.1 Description.
Influence of Other Functions via Dynamic Settings (Advanced Stage)
If available in the device, the following functions can influence the overcurrent-protection stages:
Automatic reclosing
Cold-load pickup detection
Binary input signal
The influence of these functions via dynamic settings is described in chapter 7.5.8.1 Description .
Influence of Other Functions via Dynamic Settings (Advanced Stage)
If available in the device, the following functions can influence the overcurrent-protection stages:
Automatic reclosing
Binary input signal
The influence of these functions via dynamic settings is described in chapter 7.5.8.1 Description .
Application and Setting Notes
Parameter: Method of measurement
Recommended setting value (_:781:8) Method of measurement = fundamental comp.
With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value
Description
fundamental comp.
Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value
Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 I
rated,sec
. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 I
rated,sec
multiplied by the number of
added currents.
Parameter: Type of character. curve
Default setting (_:781:108) Type of character. curve = IEC normal inverse
The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application. For more information about the parameter
Type of character. curve, refer to chapter11.9.2 Stage with Inverse-Time Characteristic Curve.
Parameter: Min. time of the curve
Default setting (_:781:113) Min. time of the curve = 0.00 s
This parameter is only available in the advanced stage.
7.5.5.2
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 651
C53000-G5040-C015-9, Edition 11.2017