Addr. Parameter C Setting Options Default Setting
_:572:9 Stage 2:Measured value
•
VA measured
•
VB measured
•
VC measured
•
VAB measured
•
VBC measured
•
VCA measured
•
VAB calculated
•
VBC calculated
•
VCA calculated
•
V0 calculated
VA measured
_:572:8 Stage 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:572:3 Stage 2:Threshold 0.300 V to 340.000 V 65.000 V
_:572:4 Stage 2:Dropout ratio 1.01 to 1.20 1.05
_:572:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s
Information List
No. Information Data Class
(Type)
Type
General
_:2311:500 General:>Current flow-criterion SPS I
_:2311:300 General:Current crit. fulf. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:571:81 Stage 1:>Block stage SPS I
_:571:54 Stage 1:Inactive SPS O
_:571:52 Stage 1:Behavior ENS O
_:571:53 Stage 1:Health ENS O
_:571:55 Stage 1:Pickup ACD O
_:571:56 Stage 1:Operate delay expired ACT O
_:571:57 Stage 1:Operate ACT O
Stage 2
_:572:81 Stage 2:>Block stage SPS I
_:572:54 Stage 2:Inactive SPS O
_:572:52 Stage 2:Behavior ENS O
_:572:53 Stage 2:Health ENS O
_:572:55 Stage 2:Pickup ACD O
_:572:56 Stage 2:Operate delay expired ACT O
_:572:57 Stage 2:Operate ACT O
7.17.6
Protection and Automation Functions
7.17 Undervoltage Protection with Any Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual 823
C53000-G5040-C015-9, Edition 11.2017