[lopauaul-100611-01.tif, 2, en_US]
Figure 7-41
Cyclic Automatic Reclosing Function - Logic of the Dead Time for the Operating Modes: With
Tripping
Dead Time for Operating Modes with Pickup
In the dead time function block, the dead time corresponding to the type of short circuit that led to the trip
command is started. The automatic reclosing operating modes with pickup are only ideal for applications with
3-pole tripping. After expiration of the dead time, the automatic reclosing function changes to the status
Switch on. Figure 7-42 shows the dead time logic.
7.2.4.12
Protection and Automation Functions
7.2 Automatic Reclosing Function
562 SIPROTEC 5, High-Voltage Bay Controller, Manual