Figure 8-19 Structure/Embedding of the Function
Function Description
The current balance is checked by a magnitude monitoring function. This function relates the smallest phase
current to the largest phase current. Unbalance is detected if
|Imin| / |Imax| < Threshold min/max, as long as Imax > Release threshold.
[losymmke-040211-01.tif, 1, en_US]
Figure 8-20 Characteristic of the Current-Balance Supervision