Addr. Parameter C Setting Options Default Setting
_:106 Inrush detect.:Operat.-
range limit Imax
1 A @ 100 Irated 0.030 A to 35.000 A 7.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 37.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 7.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 37.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 7.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 37.500 A
_:111 Inrush detect.:Blocking
with CWA
•
no
•
yes
yes
_:110 Inrush detect.:Blocking
with 2. harmonic
•
no
•
yes
yes
_:102 Inrush detect.:2nd
harmonic content
10 % to 45 % 15 %
_:112 Inrush detect.:Cross-
blocking
•
no
•
yes
no
_:109 Inrush detect.:Cross-
blocking time
0.03 s to 200.00 s 0.06 s
_:114 Inrush detect.:Start
flt.rec
•
no
•
yes
yes
Information List
No.
Information Data Class
(Type)
Type
Inrush detect.
_:81 Inrush detect.:>Block stage SPS I
_:54 Inrush detect.:Inactive SPS O
_:52 Inrush detect.:Behavior ENS O
_:53 Inrush detect.:Health ENS O
_:300 Inrush detect.:2.harmonic phase A SPS O
_:301 Inrush detect.:2.harmonic phase B SPS O
_:302 Inrush detect.:2.harmonic phase C SPS O
_:305 Inrush detect.:CWA SPS O
_:306 Inrush detect.:Cross-blocking SPS O
_:55 Inrush detect.:Pickup ACD O
7.10.6
Protection and Automation Functions
7.10 Inrush-Current Detection
766 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017