Addr. Parameter C Setting Options Default Setting
Synchr. conditions
_:5071:122 Synchrocheck 1:Max.
voltage diff. V2>V1
0.000 V to 170.000 V 5.000 V
_:5071:123 Synchrocheck 1:Max.
voltage diff. V2<V1
0.000 V to 170.000 V 5.000 V
_:5071:117 Synchrocheck 1:Max.
frequency diff. f2>f1
0.000 Hz to 2.000 Hz 0.100 Hz
_:5071:118 Synchrocheck 1:Max.
frequency diff. f2<f1
0.000 Hz to 2.000 Hz 0.100 Hz
_:5071:124 Synchrocheck 1:Max.
angle diff. α2>α1
0 ° to 90 ° 10 °
_:5071:125 Synchrocheck 1:Max.
angle diff. α2<α1
0 ° to 90 ° 10 °
Information List
No. Information Data Class
(Type)
Type
Synchrocheck 1
_:5071:81 Synchrocheck 1:>Block stage SPS I
_:5071:500 Synchrocheck 1:>Selection SPS I
_:5071:502 Synchrocheck 1:>Start / stop syn.proc. SPS I
_:5071:503 Synchrocheck 1:>Start syn. process SPS I
_:5071:504 Synchrocheck 1:>Stop syn. process SPS I
_:5071:506 Synchrocheck 1:>Op. mode 'V1<V2>' SPS I
_:5071:505 Synchrocheck 1:>Op. mode 'V1>V2<' SPS I
_:5071:507 Synchrocheck 1:>Op. mode 'V1<V2<' SPS I
_:5071:508 Synchrocheck 1:>Op. mode 'dir.cls.cmd' SPS I
_:5071:501 Synchrocheck 1:>Block close command SPS I
_:5071:54 Synchrocheck 1:Inactive SPS O
_:5071:52 Synchrocheck 1:Behavior ENS O
_:5071:53 Synchrocheck 1:Health ENS O
_:5071:328 Synchrocheck 1:In progress SPS O
_:5071:324 Synchrocheck 1:Release close cmd. SPS O
_:5071:305 Synchrocheck 1:All sync. conditio. OK SPS O
_:5071:325 Synchrocheck 1:Voltage difference OK SPS O
_:5071:326 Synchrocheck 1:Angle difference OK SPS O
_:5071:327 Synchrocheck 1:Frequency diff. OK SPS O
_:5071:307 Synchrocheck 1:Cond. V1<V2> fulfilled SPS O
_:5071:306 Synchrocheck 1:Cond. V1>V2< fulfilled SPS O
_:5071:308 Synchrocheck 1:Cond. V1<V2< fulfilled SPS O
_:5071:309 Synchrocheck 1:Frequency f1 > fmax SPS O
_:5071:310 Synchrocheck 1:Frequency f1 < fmin SPS O
_:5071:311 Synchrocheck 1:Frequency f2 > fmax SPS O
_:5071:312 Synchrocheck 1:Frequency f2 < fmin SPS O
_:5071:313 Synchrocheck 1:Voltage V1 > Vmax SPS O
_:5071:314 Synchrocheck 1:Voltage V1 < Vmin SPS O
_:5071:315 Synchrocheck 1:Voltage V2 > Vmax SPS O
_:5071:316 Synchrocheck 1:Voltage V2 < Vmin SPS O
6.4.7.4
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 379
C53000-G5040-C015-9, Edition 11.2017