Logic
[lospasym-100611-01.tif, 4, en_US]
Figure 8-13
Logic Diagram of the Voltage-Balance Supervision
The Threshold min/max parameter is the criterion by which a phase-to-phase voltage unbalance is meas-
ured. The device calculates the ratio between the minimum (V
min
) and the maximum (V
max
) phase-to-phase
voltage.
Enter the lower limit of the maximum phase-to-phase voltage (V
max
) with the parameter Release
threshold. This specifies the lower limit of the operating range of this function.
Delay failure indication
If it falls below the balance factor Threshold min/max and at the same time the maximum phase-to-phase
voltage exceeds the Release threshold, the delay of the failure indication begins, (parameter: Delay
failure indication). If both conditions persist during this time, the indication Failure is generated.
Blocking the Function
The following blockings reset the picked up function completely:
•
Externally or internally via the binary input signal
>Block function
•
A protection pickup
The pickup signal of a protection function blocks the
Failure
indication.
Application and Setting Notes
Parameter: Threshold min/max
•
Recommended setting value (_:102) Threshold min/max = 0.75
The Threshold min/max parameter is used to set the ratio between the minimum (V
min
) and the maximum
(V
max
) phase-to-phase voltage. Siemens recommends using the default setting.