Addr. Parameter C Setting Options Default Setting
_:781:41 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:781:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:107 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Information List
No. Information Data Class
(Type)
Type
General
_:2311:500 General:>Activation emg. mode SPS I
_:2311:300 General:Emergency mode act. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:781:81 Inverse-T 1:>Block stage SPS I
_:781:84 Inverse-T 1:>Activ. dyn. settings SPS I
_:781:500 Inverse-T 1:>Block delay & op. SPS I
_:781:54 Inverse-T 1:Inactive SPS O
_:781:52 Inverse-T 1:Behavior ENS O
_:781:53 Inverse-T 1:Health ENS O
_:781:60 Inverse-T 1:Inrush blocks operate ACT O
_:781:62 Inverse-T 1:Dyn.set. AR cycle1act. SPS O
_:781:63 Inverse-T 1:Dyn.set. AR cycle2act. SPS O
_:781:64 Inverse-T 1:Dyn.set. AR cycle3act. SPS O
_:781:65 Inverse-T 1:Dyn.set. ARcycl.>3act SPS O
_:781:66 Inverse-T 1:Dyn.set. CLP active SPS O
_:781:67 Inverse-T 1:Dyn.set. BI active SPS O
_:781:68 Inverse-T 1:Dyn. set. blks. pickup SPS O
_:781:59 Inverse-T 1:Disk emulation running SPS O
_:781:55 Inverse-T 1:Pickup ACD O
_:781:56 Inverse-T 1:Operate delay expired ACT O
_:781:57 Inverse-T 1:Operate ACT O
Stage with User-Defined Characteristic Curve
Description
This stage is only available in the advanced function type.
This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage (see
chapter 7.5.5.1 Description ). The only differences are as follows:
7.5.5.4
7.5.6
7.5.6.1
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 655