Settings
Addr. Parameter C Setting Options Default Setting
Definite-T 1
_:12661:1 Definite-T 1:Mode
•
off
•
on
•
test
off
_:12661:2 Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:12661:27 Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:12661:8 Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:12661:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:12661:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Definite-T 2
_:12662:1 Definite-T 2:Mode
•
off
•
on
•
test
off
_:12662:2 Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:12662:27 Definite-T 2:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:12662:8 Definite-T 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:12662:3 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:12662:6 Definite-T 2:Operate
delay
0.00 s to 60.00 s 0.10 s
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:12661:81 Definite-T 1:>Block stage SPS I
_:12661:500 Definite-T 1:>Block delay & op. SPS I
_:12661:54 Definite-T 1:Inactive SPS O
_:12661:52 Definite-T 1:Behavior ENS O
7.8.3.3
7.8.3.4
Protection and Automation Functions
7.8 Overcurrent Protection, 1-Phase
750 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017