EasyManua.ls Logo

Siemens 6MD86 - Stage with Inverse-Time Characteristic Curve

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Stage with Inverse-Time Characteristic Curve
Setting Values
Method of measurement Fundamental component
RMS value
Threshold value
67
For I
rated
= 1 A 0.030 A to 35.000 A Increments of 0.001 A
For I
rated
= 5 A 0.15 A to 175.00 A Increments of 0.01 A
Dropout Disk emulation
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Reset of the Integration Timer
Instantaneous
With dropout
Disk emulation Approx. < 0.90 ⋅ threshold value
Operate Curves and Dropout Characteristic Curves According to IEC
Extension of the operate time during operation with
transformer inrush-current detection
Approx. 10 ms
The operate curves and dropout characteristic curves according to IEC can be found in the Technical Data
chapter under Inverse-Time Overcurrent Protection.
Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE
The operate curves and dropout characteristic curves according to ANSI/IEEE can be found in the Technical
Data chapter under Inverse-Time Overcurrent Protection.
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active
11.15
67
If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
rated,sec
.
Technical Data
11.15 Stage with Inverse-Time Characteristic Curve
SIPROTEC 5, High-Voltage Bay Controller, Manual 1145
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals