Application and Setting Notes
Parameter: Threshold
•
Recommended setting value (_:1981:3) Threshold = 10 %
The setting of the parameter Threshold depends on the respective application. A threshold value of 10 % is
a practicable value for fault indications of electrical machines.
Parameter: Operate delay
•
Recommended setting value (_:1981:6) Operate delay = 1500 ms
The setting of the Operate delay depends on the application. Observe the time grading in the power-
system protection and do not set the time for monitoring too short. The default setting is practicable. For
motors, the time depends on the permissible time period for the set unbalanced load.
Parameter: Blk. w. inrush curr. detect.
•
Default setting (_:1981:104) Blk. w. inrush curr. detect. = no
With the parameter Blk. w. inrush curr. detect., the stage can be stabilized against tripping on
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to yes.
Settings
Addr.
Parameter C Setting Options Default Setting
General
_:2311:106 General:Reference value
•
pos. seq. current
•
rated current
rated current
_:2311:107 General:Current limita-
tion Imax
•
no
•
yes
no
_:2311:101 General:Maximum phase
current
1 A @ 100 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 10.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 50.000 A
_:2311:104 General:Release current 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
Definite-T 1
_:1981:1 Definite-T 1:Mode
•
off
•
on
•
test
off
_:1981:2 Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:1981:3 Definite-T 1:Threshold 5.0 % to 999.9 % 10.0 %
_:1981:4 Definite-T 1:Dropout
ratio
0.40 to 0.99 0.95
_:1981:104 Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
7.25.4
7.25.5
Protection and Automation Functions
7.25 Negative-Sequence Protection