Parameter Value Description
yes
Use this setting when switching procedures (opening of the CB) are not
permitted to result in stage pickup.
Note that pickup is delayed by approximately 40 ms. This delay is added to
the operate time.
Parameter: Charact. constant k, Charact. constant α, Charact. constant c
Default setting (_:103) Charact. constant k = 1.00
Default setting (_:104) Charact. constant α = 1.000
Default setting (_:105) Charact. constant c = 0.000
With the Charact. constant k, Charact. constant α, and Charact. constant c parameters,
you define the required inverse-time characteristic.
Parameter: Time dial
Default setting (_:106) Time dial = 1.00
With the Time dial parameter, you displace the characteristic curve in the time direction.
As usually, there is no time grading for voltage protection and therefore no displacement of the characteristic
curve, Siemens recommends leaving the Time dial parameter at 1.00 (default setting).
Parameter: Reset time
Default setting (_:108) Reset time = 0.00 s
With the Reset time parameter, you define the reset time delay which is started when the voltage exceeds
the dropout value. Set the parameter Reset time to 0 s when instantaneous reset is desired.
Under network conditions of intermittent faults or faults which occur in rapid succession, Siemens recom-
mends setting the Reset time to an appropriate value > 0 s to ensure the operation. Otherwise, Siemens
recommends keeping the default value to ensure a fast reset of the function.
Parameter: Additional time delay
Default setting (_:107) Additional time delay = 0.00 s
With the Additional time delay parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, only the inverse-time delay is operative.
Settings
Addr.
Parameter C Setting Options Default Setting
Inverse-T #
_:1 Inverse-T #:Mode
off
on
test
off
_:2 Inverse-T #:Operate &
flt.rec. blocked
no
yes
no
_:10 Inverse-T #:Blk. by
meas.-volt. failure
no
yes
yes
_:9 Inverse-T #:Measured
value
phase-to-ground
phase-to-phase
phase-to-phase
_:8 Inverse-T #:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
7.16.9
Protection and Automation Functions
7.16 Undervoltage Protection with 3-Phase Voltage
816 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017